πŸ”§ Vaillant πŸ”§ Viessmann πŸ”§ Protherm πŸ”§ Daikin πŸ”§ Panasonic & Mitsubishi πŸ”§ Fronius / GoodWe / Solax πŸ”§ Bosch / Siemens πŸ”§ AEG / Electrolux πŸ”§ LG & Samsung πŸ”§ DeLonghi / Philips / Krups πŸ”§ Baxi & De Dietrich πŸ”§ Junkers / Buderus / Bosch πŸ”§ Panasonic Aquarea & NIBE πŸ”§ Solax / Huawei / Growatt πŸ”§ Whirlpool & Indesit πŸ”§ Beko πŸ”§ Gorenje & Mora πŸ”§ Krups / Jura / Nivona πŸ”§ Bosch eBike / Bafang / Shimano πŸ”§ Xiaomi & Ninebot πŸ”§ Husqvarna / Gardena / Parkside πŸ”§ Webasto & EberspΓ€cher
Technical Diagnostics & Fault Codes β€’ Gas Condensing Boilers (Junkers Cerapur, Buderus Logamax & Bosch Condens)

Junkers, Buderus & Bosch Error Codes: EA / 6A, CE / H07, A7, C6, E9 – Error Code Meaning, Troubleshooting & Repair

Complete diagnostic table of the most common faults for Junkers / Buderus / Bosch (Gas Condensing Boilers (Junkers Cerapur, Buderus Logamax & Bosch Condens)) with quick troubleshooting steps and links to replacement parts:

Error Code Reference Table for Junkers / Buderus / Bosch and step-by-step repair procedure:

Error Code Meaning / Fault Symptom Most Common Cause & Repair Procedure
EA / 6A (227) No flame detected after ignition attempt (missing ionization current) Check that the main gas shut-off valve is open, clean the condensate trap, and inspect the ignition/ionization electrode; fluctuating gas supply pressure or a faulty control board are also common causes.
CE / H07 (1017) Low water pressure in the heating system (below the 0.6 bar minimum threshold) Refill the heating circuit via the filling loop to 1.2 – 1.5 bar; if the pressure rapidly climbs toward 3 bar when heated, the expansion vessel diaphragm has lost its air charge.
A7 / AD Faulty domestic hot water temperature sensor (DHW / cylinder NTC probe) Broken wire or defective NTC thermistor for hot water heating in the storage tank or plate heat exchanger; measure the sensor resistance with a multimeter and replace the NTC probe.
C6 / 3C (215) Flue gas fan not running or air pressure switch (manostat) failed to close Differential pressure switch silicone tubes blocked by condensate, obstructed coaxial flue pipe, or worn flue fan bearings.
E9 / D4 (224) Heat exchanger safety temperature limiter (STB) tripped Insufficient water flow through the primary heat exchanger – verify circulation pump operation, open radiator thermostatic valves, and bleed the pump.